CompTIA A+ Core 1 (220-1201) free question 5 / 10 · Domain 3: Hardware
A contractor wants to reuse installed Cat 6 cabling for a 10GBASE-T link to a workstation 60 meters from the switch. What does the Fluke cabling table say about this plan?
- Cat 8 is the lowest category listed for 10GBASE-T over a 60 m run
- Cat 6 is listed for 10GBASE-T to 35 m, so a 60 m run needs Cat 6A or better
- Cat 6 is listed for 10GBASE-T over a full 100 m channel, so the run works
- Cat 5e carries 10GBASE-T at 100 MHz, so the run can use Cat 5e instead
Show the answer and explanation
Answer: B
Why this is correct
The Fluke Networks table of cabling standards lists the maximum frequency and the network standards each category supports, and notes that support is for 100 meter channels unless otherwise indicated. The CAT 6 row (Class E, 250 MHz) shows 10GBASE-T with a 35 m maximum, which falls short of a 60 m run. The CAT 6A row (Class EA, 500 MHz) carries a check under 10GBASE-T with no length limit, so Cat 6A or better is needed for the 60 m link. Reusing the installed Cat 6 would work only up to 35 meters.
Why the other options are wrong
"Cat 8 is the lowest category listed for 10GBASE-T over a 60 m run" … The table marks 10GBASE-T for Cat 6A with a check as well, and Cat 6A is rated to 500 MHz. Cat 8 is the row for 25/40GBASE-T with a 30 m maximum.
"Cat 5e carries 10GBASE-T at 100 MHz, so the run can use Cat 5e instead" … The Cat 5e row is rated to 100 MHz and carries a check for 1000BASE-T. It has no mark under 10GBASE-T.
"Cat 6 is listed for 10GBASE-T over a full 100 m channel, so the run works" … The table footnote gives 100 meter channels unless otherwise indicated, and the Cat 6 row is indicated otherwise with a 35 m maximum for 10GBASE-T.
Key points
The same page notes that the vast majority of installed cabling is Cat 5e and that moving to 10GBASE-T would mean replacing it with Cat 6A or better.